SILV-1000LT Resistive AC Load Bank For Generator or Power Testing

Keyword:

Product Introduction

The Rata SILV-1000LT three-phase resistive load bank is a cost-effective professional load simulation device integrating 1000kW ultra-high power, 10kW coarse-grained control, industrial-grade heat dissipation and multi-layer safety protection with vertical compact design.

 

It is widely used for performance testing and verification of industrial power supplies including large generators, UPS systems and transformers.

Main Parameters

Model No.SIL-V-1000L
Country of originChina
Max capacity1000kW
Rated testing voltage400Vac
Frequency50Hz.
Phases3
Wire(Star connection)4
Load step resolution1 kW
Load step (kW)1+2+2+5+10+10+20+60+100+200*4
Voltage Tolerance (Short Term Operation)+5%
Load Element Tolerance± 6%
Insulation Test500Vac
Load ConnectionsCopper busbars
ProtectionThermal emergency cut out
Air-flow switch
Fan overload protection
Emergency stop
ACH-Schneider EVS 2000A, # Isolator
Control powerFrom internal main's load circuit
Cooling methodAir forced cooling
Airflow volume(Approx. CMM)50m3/kW/ h
Airflow directionHorizonts
Load switching/contactor type3 pole AC contactors
Rated maximum ambient temp. operation+60°C / +122°F
Rated minimum ambient temp. operation-20°C/-4°F
Altitude rating<2000m [m.a.s.l.]
Control chamber IP ratingIP 84
Portability2 folkift holes
Enclosure dimentions
Length(mm)2230
Depth(mm)1430
Height(mm)2068
Weight(KG)1500
Load bank control system
Manual controlPush buttons
Remote controlUpper level PO based software
CommunicationModbus TCP
Test voltage(3 phases)Power derating with lower voltage applied.
400V1000 kW
380V900 kW

CONSULT