Schneider B265L 265kW resistive AC load bank For UPS Testing
Keyword:
Product Introduction
The B265L 265kW AC resistive load bank, manufactured under authorization from Schneider, is a professional load simulation equipment integrating an ultra-high power of 265kW, 1kW fine stepping, industrial-grade heat dissipation, rapid deployment, and multiple safety protections.
It is widely used for performance testing and verification of industrial power supplies such as large generators, UPS systems, and transformers.
Key Features
(1)Ultra-high power design:Meets heavy load demands;
(2)Precise load control:1kW level stepping;
(3)Industrial-grade heat dissipation system:Ensures sustained efficient operation;
(4)Fin-type resistor design:High efficiency and durability;
(5)Quick connector design:Plug-and-play;
(6)Containerized design:Easy transportation and deployment;
(7)Multiple safety protections:Ensures reliable operation;
(8)Flexible control system:Supports multiple operating modes.
Engineering drawing
![]() | ![]() |
![]() | ![]() |
Main Parameters
| Model No. | B265L |
| Country of origin | China |
| Max capacity | 265kW |
| Tested voltage | 400Vac |
| Frequency | 50/60Hz. |
| Phases | 3 |
| Wires(Star connection) | 4 |
| Load step resolution | 1kW |
| Voltage Tolerance (Short Term Operation) | +6% |
| Load Element Tolerance | ± 5% |
| Insulation Test | 500Vac |
| Load Connections | 400A cam lock quick connector |
| Protection | Thermal emergency cut outAir flow switchControl and mains circuit overload protectionEmergency stop |
| Control voltage | Optional 400Vac |
| Cooling method | Air forced cooling |
| Airflow volume(Approx.) | 70 CBM/KW/Hour |
| Airflow direction | Horizontal |
| Load switching contactor type | AC 3 pole contactors |
| Rated maximum ambient temp. operation | +50°C / +122°F |
| Rated minimum ambient temp. operation | -20°C / -4°F |
| Altitude rating | <2000m [m.a.s.l] |
| Ccontrol chamber IP rating | IP 55 |
| Portability | 4 universal casters& 2 folkift pockets |
| Stackable | Yes |
| Enclosure dimensions | |
| Width(mm) | 1478 |
| Depth(mm) | 1160 |
| Height(mm) | 1100 |
| Weight(KG) | 295 |
| Load bank control system | |
| Manual control | Push buttons |
| PLC control | Remote PC control with software Nexus-1 |
| Power deration with voltage applied | |
| 400V | 265 kW |
| 380V | 240 kW |
Key details
![]() | ![]() |
![]() | ![]() |
CONSULT
NOW
If you have any suggestions or feedback on our company, please fill in the relevant information on this page and submit it. A staff member will contact you in time, or please call us directly.