1800 kW AC Resistive Load Bank For Generator Testing or UPS

Keyword:

Product Introduction

 

The Rata SIRL-1800kW AC resistive load bank is a professional load simulation testing solution integrating ultra-high power of 1800kW, precise 5kW step control, industrial-grade heat dissipation, intelligent management and comprehensive protection functions.

 

It is widely used for performance testing and verification of large-scale industrial power equipment including large generators, UPS systems, data centers and energy storage systems.

 

ENCLOSURE DRAWINGS

 

未标题-1 (29)

Main Parameters

 

Rated power1800kW
Power factor1.0
Rated load voltage.400vac
Hz.50Hz.
Phase & wires3P4W
Load resolution5kW
Voltage Tolerance (Short Term Operation)+5%
Load Element Tolerance± 3%
Load connectionCopper busbar
Control powerATS Int/Ext Bascule
Control voltage400Vac
Enclosure Structure
Canopy/ containerContainer
Noise level85±3dB(A)
Size(Width*Depth*Height mm)2000*2950*2350
Weight2400kgs
Air directionHorizontal
Quantity of fans4*  3kW
Air volume(m³/kW/hour)70
PortabilityISO lifting&locking points
IP grade of control chamber55
IP grade of complete enclosure54
Load Bank Control
Temperature-20 °C to +50°C
Latitude≦2000 m.a.s.l
Load swithing3 Pole contactor
Digital meterV/A/kW/Hz/Pf.
InterfaceRJ45
Type of communicationModbus TCP
Local controlBouton
Remote controlPC based software
Power Derate At Other Voltages
400Vac1800kW
380Vac1625kW
220Vac545kW

Key details